750 kVA, 3-Phase Padmount Transformer Supply and Delivery
Defense Health Agency (dha) — DEFENSE HEALTH AGENCYBeaufort, South Carolina#HT940627QE008
The Defense Health Agency (DHA) is seeking a single 750 kVA, 3-phase padmount transformer for delivery to Naval Hospital Beaufort, SC. The transformer must be new, meet strict technical specifications, and be delivered as soon as possible. Bidders must submit one electronic quote via email to Yuleiny Garcia and Michael Heaney, with the RFQ number in the subject line. The quote must include technical compliance, delivery lead time, and a firm-fixed-price quote. All bidders must be registered in SAM and complete annual representations.
On PublicBidSearch: the original bid posting, 1 bid document and the agency contact (name and email) for this bid.
Contact
Agency contact for this bidName and email — included with ProProOverview
- Due
- Nov 9, 2026
- Time stated in bid documents
- Nov 9, 2026, 9:00 AM Eastern Time
- Submission
- Documents analyzed
- 1
- Required submission items
- 4 items · full checklist with Pro
Scope of work
- New unit, not used, reconditioned, or remanufactured
- High voltage: 4160V Delta, 60 kV BIL, with specified taps
- Low voltage: 480Y/277V, 30 kV BIL
- Dead-front loop feed design with six 200A wells and inserts
- Four 6-hole spades on low-voltage side
Steps to Bid
- 1
Register in SAM and complete annual representations and certifications via SAM.
- 2
Prepare and submit one electronic quote via email to Yuleiny Garcia and Michael Heaney, with the subject line: 'RFQ HT940627QE008'. was Nov 9, 2026, 9:00 AM
This date has passed — confirm eligibility with the agency before bidding.
- 3
Ensure the quote is in a format readable by Microsoft Office 365 (Word, Excel) or Adobe Acrobat (searchable PDF), and not locked, encrypted, or password-protected.
What you'll need
Submission
NAICS
335311
Get alerts for bids like this
New electrical bids in South Carolina
This bid has closed. We'll tell you when the next one like it posts. Free, no card needed.
Get alerts — freeProject details
The transformer must meet the following technical specifications: high voltage of 4160V Delta, 60 kV BIL, with specified taps; low voltage of 480Y/277V, 30 kV BIL; dead-front loop feed design with six (6) 200A wells and inserts, four (4) 6-hole spades on the low-voltage side; mineral oil filled with 65°C temperature rise and ONAN cooling; aluminum windings (Al/Al); bayonet fusing with isolation links; three (3) 2-position LBOR switches; full complement of gauges, valves, and standard accessories per IEEE C57.12.34. Delivery is required as soon as possible due to the critical nature of the facility and current reliance on emergency generators. The work shall be performed at Naval Hospital Beaufort, Building 1, 1 Pinckney Blvd, Beaufort, SC 29902. The quote must be in a format readable by Microsoft Office 365 (Word, Excel) or Adobe Acrobat (searchable PDF), and must not be locked, encrypted, or password-protected. Offerors must be registered in the System for Award Management (SAM) and complete annual representations and certifications via SAM. Payment will be made via Electronic Funds Transfer (EFT) through DFAS using WAWF.
Documents
- RFQ_HT940627QE008.pdf9 pages
Closing soon near Beaufort
- Integrated Custodial Grounds and Facilities Maintenance Services · Ridgeland · closes Dec 1, 2026
- As-Needed Professional Survey Services FY27-FY31 RFQu · Bluffton · closes Dec 2, 2026
- Investment Broker Services · Hilton Head Island · closes Dec 2, 2026
- Argent & Sundance Traffic Signal Construction · Hardeeville · closes Dec 3, 2026
- Crossings Park Improvements Phase 1-Pickle Ball Courts & Arrow Road · Hilton Head Island · closes Dec 3, 2026