Calawah Substation Transformer - 3-Phase, 12/16/20 MVA, No Load Tap Changer
Clallam County PUDSequim, Washington#260809
The Clallam County PUD is soliciting sealed bids for one 3-phase, 12/16/20 MVA power transformer without Load Tap Changer for the Calawah Substation. The transformer must be oil-immersed, 60 Hz, with a self-cooled rating of 12,000 kVA, 16,000 kVA, and 20,000 kVA. The high-voltage side is 69,000 V delta with a BIL of 350 kV; the low-voltage side is 12,470/7,200 V wye with a BIL of 110 kV. Impedance is 8.5% at 12,000 kVA or 20,000 kVA base. Cooling class is ONAN/ONAF/ONAF. The transformer must include factory testing, manufacturer’s standard warranty, bushings, cooling system, oil preservation system, and a weatherproof terminal box. Bidders must provide certification of BABA compliance. Used/refurbished transformers will be evaluated using a weighted value formula: (Bid price) × (50 / (50 - age)) = Weighted Value Bid. No-load and load losses will be evaluated at $6,330.00/kW and $2,120.00/kW, respectively. Excess losses will be deducted as liquidated damages. Delivery must be scheduled two (2) weeks prior to arrival, Monday–Thursday, 7:00 a.m.–3:00 p.m., with vehicle height not exceeding 14’6”. A three-way impact recorder must be mounted. The transformer must be shipped with oil and be pressure-tested for 8 hours at maximum operating pressure. Bidders must submit a drawing of the coil bracing system, a list of previously tested medium power transformers, and a complete listing of all full-sized transformers tested for short-circuit capability. The bid must be accompanied by a Bid Bond, Certified Check, or Cashier’s Check in the amount of 5% of the bid total. The District reserves the right to reject any or all bids.
On PublicBidSearch: the original bid posting, 1 bid document and the agency contact (name, email and phone) for this bid.
Contact
Agency contact for this bidName, email and phone — included with ProProOverview
- Due
- Dec 3, 2026
- Time stated in bid documents
- Dec 3, 2026, 2:30 PM Pacific Time
- Bid bond
- 5%
- Performance bond
- 100%
- Submission
- mail, hand delivery
- Contract term
- 120 calendar days from Notice to Proceed
- Documents analyzed
- 1
Scope of work
- Deliver FOB Destination to Calawah Substation, Forks, WA
- Provide certification of BABA compliance for all materials and equipment
Steps to Bid
- 1
Register on the plan holder list by emailing [email available with Pro].
- 2
Download the bid packet from Official linkPro.
- 3
Submit questions to Doug Adams at [email available with Pro] by 12:00 p.m. Pacific Time on November 23, 2026. was Nov 23, 2026, 12:00 PM
This date has passed — confirm eligibility with the agency before bidding.
- 4
Prepare the bid proposal, including the completed Proposal form, required drawings, and supporting documentation.
- 5
Attach a Bid Bond, Certified Check, or Cashier’s Check in the amount of 5% of the bid total.
- 6
Submit the sealed bid envelope to the Contracts Coordinator at PUD No. 1 of Clallam County, 100 Hooker Road, Sequim, WA 98324, by 2:30 p.m. Pacific Time on Thursday, December 3, 2026. by Dec 3, 2026, 2:30 PM
- 7
Attend the public bid opening at 3:00 p.m. Pacific Time on December 3, 2026, in the Boardroom at the District’s Main Office, 104 Hooker Road, Sequim, WA. by Dec 3, 2026, 3:00 PM
What you'll need
Submission
Mail, Hand delivery
NAICS
335918, 335919
Pursuit snapshot
Pro- Go / no-go verdict on every requirement
- 9 watch-outs that disqualify bidders
Cancel anytime · no card to browse
Project details
One (1) quantity new, rebuilt, or reconditioned 3-phase, 12/16/20 MVA power transformer without Load Tap Changer, as specified in Section III – Specifications for Calawah Transformer. The transformer must be oil-immersed, 60 Hz, rated for 55°C average winding temperature rise and 80°C hot spot winding temperature rise, with a self-cooled rating of 12,000 kVA, 16,000 kVA, and 20,000 kVA. Must include factory testing, manufacturer’s standard warranty, and all required accessories: bushings (high-voltage: 400 A, 450 kV BIL, 72 in creepage; low-voltage: 1,200 A, 150 kV BIL, 17 in creepage), cooling system with fans, pumps, and control relays, oil preservation system with nitrogen pressure control, and a weatherproof terminal box.
Key dates
- Questions due
- Nov 23, 2026, 12:00 PM Pacific Time
- Bids due
- Dec 3, 2026
Documents
- 260809-Bid-Packet-1.pdf43 pages
Similar bids near Sequim
- Gorge Powerhouse Crane Replacement · Seattle · closes Nov 30, 2026
- Solid-Dielectric Medium Voltage Switchgear · Seattle · closes Jan 14, 2027
- 2027 Airfield Projects – Contract 1: Pavement, Lighting, Utilities, and Safety Infrastructure Replacement at Seattle… · Seattle · closes Dec 16, 2026
- RFP-Low-Med Voltage Transformer Inspection, Analysis and Diagnostics · Seattle · closes Dec 4, 2026
- Electrical Unit Price Portwide 2027 · Seattle · closes Dec 22, 2026
Closing soon near Sequim
- Landfill Post-Closure Support Services for Solid Waste Permit Compliance · Port Angeles · closes Nov 30, 2026
- Sol Duc Bridge Painting Contract · Port Angeles · closes Dec 1, 2026
- Security Services at Clallam County Courthouse and Juvenile and Family Center · Port Angeles · closes Dec 1, 2026
- Airline Technical Representative Services · Seattle · closes Dec 1, 2026
- Office Space Lease in Port Angeles and Sequim, WA · Sequim · closes Dec 4, 2026